Product No : TFC63_Series
Product Description

The TFC63 series are three phase output AC power source, output capacity from 500VA to 800kVA. Adopting PWM high frequency technology & IGBT regulation mode, the TFC63 series features constant frequency and voltage with high accuracy. The TFC63 series can be used to simulate grids of different countries, widely used in laboratories, production calibration & test and military applications.

  • RS485.jpg
  • RS232.jpg

★ Output voltage: phase voltage 1~300V, line voltage 1~520V, resolution 0.1V

★ Output frequency: 45-65Hz adjustable, fixed 50Hz and 60Hz

★ Fast output key for 110/220V and 50/60Hz

★ Phase difference: 120°±2°

★ High accuracy LED display for voltage, current, frequency, active power, power factor

★ Fast transient response, response time no more than 2ms for 100% load and unload

★ Multiple protections: OVP, OCP, OTP and OLP

★ Optional: RS-232/RS-485 interface for PC remote control on output frequency and voltage

★ Optional: DC0-5V analog input for output control

★ Customized specifications and functions acceptable

Circuit mode

IGBT/PWM

Output

Phase

3 phase, Phase difference: 120°±2°

Low range

Phase voltage 1.0V-150.0V, Line voltage 1.0-260.0V

High range

Phase voltage 1.0V-300.0V, Line voltage 1.0-520.0V

Frequency

45-65Hz adjustable, fixed 50Hz and 60Hz

Fast output key for 50/60Hz

Voltage accuracy

±1% (110Vor220V ±10%)

±1.5% (other range)

Frequency stability

≤0.1%

Voltage stability

±1%

Harmonic distortion

±2% (resistive load)

Crest factor

1.41±0.10

Line regulation

≤1%

Load regulation

≤1%

Efficiency

≥85%

Response time

Max. 2ms

3 phase voltage unbalance

Can be connected to unbalanced load, can be used as single phase

Meter & Resolution

Frequency meter

4 digits LED, resolution 0.1Hz

Voltmeter

4 digits LED, resolution 0.1V

Ammeter

4 digits LED, resolution 0.001A / 0.1A

Power meter

4 digits LED, resolution 0.01W/ 0.1kW

Insulation

Transformer insulated

Preset function

Preset output voltage, output frequency and output voltage floating ratio

Fast key function

Fast key for output voltage switch, frequency switch, output voltage floating selection

Alarm function

Audio and visual alarm started once protection device is activated. Error code will be displayed.

Protection

Fuse switch for input and output;

Fast-response circuit to detect over voltage, over current, over load, over temperature and short circuit; Output will be shut down in protection mode.

Cooling

Cooling fan

Cabinet protection grade

IP2X

Operation environment

0-40, ≤90% RH(Non-condensing), Altitude: 1500 feet

Model

Total

Capacity

Max.Current

Input

N.W

(kg)

G.W.

(kg)

Dimension

(mm)

Low range

@110V

High range

@220V

TFC-6303

3KVA

9A

4.5A

1P 220Vac

75

90

420W*520H*580D

TFC-6306

6KVA

18A

9A

3P 380Vac

150

175

500W*900H*680D

TFC-6310

10KVA

30A

15A

3P 380Vac

170

200

500W*900H*680D

TFC-6315

15KVA

46A

23A

3P 380Vac

200

240

500W*900H*680D

TFC-6320

20KVA

60A

30A

3P 380Vac

260

300

590W*1100H*800D

TFC-6330

30KVA

90A

45A

3P 380Vac

300

360

590W*1100H*800D

TFC-6345

45KVA

136A

68A

3P 380Vac

420

500

720W*1220H*1080D

TFC-6360

60KVA

180A

90A

3P 380Vac

500

580

720W*1220H*1080D

TFC-6375

75KVA

226A

113A

3P 380Vac

530

610

750W*1300H*1382D

TFC-6390

90KVA

272A

136A

3P 380Vac

650

730

750W*1300H*1382D

TFC-63100

100KVA

303A

151A

3P 380Vac

700

820

750W*1300H*1382D

TFC-63120

120KVA

364A

182A

3P 380Vac

800

900

1380W*1450H*870D

TFC-63150

150KVA

454A

227A

3P 380Vac

1000

1100

1380W*1450H*870D

TFC-63180

180KVA

546A

273A

3P 380Vac

1200

1320

2100W*1650H*1350D

TFC-63200

200KVA

606A

303A

3P 380Vac

1400

1520

2100W*1650H*1350D

TFC-63250

250KVA

757A

378A

3P 380Vac

1500

1620

2100W*1650H*1350D

TFC-63300

300KVA

909A

455A

3P 380Vac

1850

1970

2600W*1800H*1550D

TFC-63450

450KV

1363A

681A

3P 380Vac

2200

2350

2600W*1800H*1550D

More models are available at request.